Audited by an independent third-party inspection agency
Cooling capacity: 35W/K to 90W/K
Cooling Capacity | W/K | 35 | 60 | 80 | 90 | |
Heater | W | Optional | 300,500 | 500,800,1000 | ||
Air flow | m3/h | Internal air flow | 200 | 360 | 480 | 550 |
Fan type | NA | Backward Centrifugal fan | ||||
Static pressure Inter. | Pa | Internal fan outlet pressure | >100 | |||
Temp. | ºC | Operating range | -40~70 degree 0-100%RH | |||
Noise | dB(A) | 3m,awayETS300-753 | 45 | 50 | 52 | 54 |
Dimension | mm | WxDxH | 365x150x750 | 380x150x800 | 450x150x950 | 450x190x1150 |
Weight | Kg | Net Weight | 15 | 21 | 30 | 38 |
Power consumption | W | DC Version:48V | 50 | 80 | 120 | 150 |
AC Version:230V/110V | 55 | 90 | 145 | 165 | ||
Voltage | V | Rated | DC:48V AC:230V/110V | |||
Safety | EN60950 | CE/TUV/CCC | ||||
IP | IEC6052 | >=IP55 | ||||
Frequency | Hz | Rated | 50/60 |
Cooling Capacity | W/K | 110 | 120 | 150 | 180 | |
Heater | W | Optional | 500,800,1000 | 800,1000,2000 | ||
Air flow | m3/h | Internal air flow | 650 | 700 | 900 | 1100 |
Fan type | NA | Backward Centrifugal fan | ||||
Static pressure Inter. | Pa | Internal fan outlet pressure | >100 | |||
Temp. | ºC | Operating range | -40~70 degree 0-100%RH | |||
Noise | dB(A) | 3m,awayETS300-753 | 55 | 57 | 57 | 57 |
Dimension | mm | WxDxH | 450x190x1150 | 450x190x1150 | 450x240x1300 | 600x240x1350 |
Weight | Kg | Net Weight | 38 | 38 | 42 | 50 |
Power consumption | W | DC Version:48V | 180 | 200 | 200 | 275 |
AC Version:230V/110V | 200 | 220 | 220 | 300 | ||
Voltage | V | Rated | DC:48V AC:230V/110V | |||
Safety | EN60950 | CE/TUV/CCC | ||||
IP | IEC6052 | >=IP55 | ||||
Frequency | Hz | Rated | 50/60 |